price | 1 | Gas Fired Steam Boiler (100KG/H, LSS0.05-0.7-Q) | Boiler body |
Instrument & valves (all Chinese brand) | |||
Electric control box | |||
Gas burner (Baltur, Italy) | |||
Water pump (Zhejiang) | |||
2 | 200L/H Water Softener (Model HX-255/440-200,Model) | ||
3 | Cold Water Tank | ||
Delivery Time | 1 weeks upon receipt of payment | ||
Packing Method | Plywood case |
Item | Material / Model | Supplier | Qty | |
Boiler body (fibre glass insulated) | 20# carbon steel | Shanghai | 1 set | |
Water magnetizer | Made in Shanghai | 1 set | ||
Instruments and valves | Flange type stop valve(for steam outlet) | DN15 | 1 pc. | |
Ball valve (for water inlet) | DN15 | 1 pc. | ||
Check valve (for water inlet) | DN15 | 2 pcs | ||
Flange type blowdown valve | DN20 | 1 pc | ||
Flange type blowdown valve (for steam separator) | DN20 | 1 pc | ||
Flange type safety valve | DN25 | 1 pc | ||
Pressure controller | P10, CE verified | FENSHEN | 1 pc | |
Pressure gauge | 100-1.6 | Made in Zhejiang | 1 pc | |
Pressure gauge with electric contact | Y-150D | 1 pc. | ||
Water level gauge | 1 pc. | |||
Water level electrode with ball valve | Stainless steel 304 | Shanghai | 1 set | |
Steam seprator | 1 set | |||
Electric control box | DELIXI | 1 set | ||
AC contactor | 1801 | 1 pc. | ||
Gas burner (made in Italy) | Baltur | 1 set |
Item | Material / Model | Supplier | Qty. |
0.2m3 Water Tank | Steel / HZS-200 | Shanghai | 1 set |
Item | Material | Supplier | Qty. |
Base Frame (with piping work on it) | Steel | Shanghai | 1 set |
Model Items | LSS0.05-0.7-Q | |
Boiler horsepower | 6.4HP | |
Rated steam output | 100 KG/HOUR | |
Maximum working pressure | (manual reset)<0.7MPa / 102PSI | |
Saturated steam temperature | <172°C | |
Material of main body | 20# carbon steel | |
Thickness of main body | 12mm | |
Thermal efficiency | >92% | |
Natural gas | 8m3/h | |
Dimensions after installation | Φ | 710mm |
H | 1475mm | |
Packing dimensions | L | 890mm |
W | 1050mm | |
H | 1700mm |
Item | Water Quality Standard of Industrial Steam Boiler (GB1576-2001) | |
Feed water | Boiler water | |
Suspended solids | <=5 mg/L | 0 |
Total hardness | <=0.03 mmol/L | 0 |
PH (25℃) | >=7 | 10-12 |
Dissolved oxygen | <=0.1 mg/L | 0 |